312
Power Quality Event Retrieve Address
Power quality event includes timestamp, triggering condition and related
settings. Every group uses the same data format. Only 10 groups of data are
saved in the registers. When retrieving the event data, its parameters must be
correctly set in order to get correct information.
Read: FC03, Preset: FC16. For more information, please refer to Chapter 4.7.
Table 6-57
Address Parameter Data Type Property Range Default
Factory
Settings
8CFDH
Newest Event
Group Number
word R
1—50000
0: No Data
0 0
8CFEH
Event for
Retrieving
starting group
number
word R/W
1-50000
Note: only valid
smaller or equal
to Newest Event
Group Number
1 1
8CFFH
No.1 Event
8D00H
Timestamp
High Byte –
Year Low Byte -
Month
word R Time
8D01H
Timestamp
High Byte –Day
Low Byte -Hour
word R Time
8D02H
Timestamp
High Byte –
Minute Low
Byte - Second
word R Time
8D03H
Timestamp:
Millisecond
word R Time