78
“Delay time (1051H)” is set to 500, so the actual delay time is 500*10ms=5s.
“Output to relay (1052H)” is set to 0, because there is no output to RO.
Settings of second group:
“Parameter code (1053H)” is set to 1, which stands for U1.
“Comparison mode (1054H)” is set to 3, which stands for "smaller than".
“Setpoint value (1055H)” is set to 998, according to the relationship between
actual value and communication value (U=Rx X (PT1/PT2) /10).
“Delay time (1056H)” is set to 1000, so the actual delay time is 1000*10ms=10s.
“Output to relay (1057H)” is set to 0, because there is no output to RO.
Global settings:
“Alarming channel enable setting (1048H)” set to 0003H to enable the rst and
the second channel.
“Logic "AND" between alarming setting (1049H)” set to 0001H to enable logic
"AND" in Pair 1.
“Alarming output to DO1 setting (104AH)” set to 0, since no output to DO1.
“Alarming output to DO2 setting (104BH)” set to 0.
“Alarming output to DO3 setting (104CH)” set to 0.
“Alarming output to DO4 setting (104DH)” set to 0.
“Alarming flash enable (1047H)” set to 0 to disable backlight flashing when
alarming occurs.
“Global alarming enable (1046H)” set to 1 to enable over/under limit alarming.