Switch off the power supply to protect power cord when overcurrent occurs.
Make sure to use the breaker between power supply and interference filter that conforms to
IEC specification and UL recognition in accordance with the User manual.
Please use the breaker with leakage function recommended by ACTION TECHNOLOGY in
order to meet EMC standards.
To prevent the outside interference from power cables.
Please use the interference filter recommended by ACTION TECHNOLOGY in order to
meet EMC standards.
Switch main power supply (ON/OFF). And use it after installing a surge absorber.
Please use the surge absorber recommended by ACTION TECHNOLOGY in order to meet
EMC standards.
Interference filter for signal
cable / ferrite filter
Please use the interference filter recommended by ACTION TECHNOLOGY in order to
meet EMC standards.
This product is not equipped with regenerative resistor.
The external regenerative resistor is necessary when the internal capacitor cannot absorb
more regenerative power. Confirm the regenerative status on the panel. When the
regenerative voltage alarm is ON, a regenerative resistor is needed.
For the reference specification of regenerative resistor, please refer to user manual.
Use a built-in thermostat and set overheat protect circuit.
This product belongs to Class 1 and need grounding protection.
Using protection grounding terminal. Grounding should be executed by the case and cabinet
that conforms to EMC.
The following symbol indicates the protection grounding terminal.