Specifications:
Class A – Indoor IP30 0°C to 40°C
Weight (excluding batteries)
Cable Entries (20mm knockouts)
200V-240V (+10%, -15%), 50/60Hz AC, 1.0A max
24V DC, 3A High Efficiency Switched Mode [2A load, 1A battery charging]
Ripple: 200mV max. (Note: 1V p-p including switching frequency noise)
Imax(a) = 1.2A
1
, Imax(b) = 3.0A
2
Battery Capacity and Battery
Internal Resistance
24V 4Ah Internal (min), 24V 7Ah Internal (max)
1.6Ω
1.0A Temperature Compensated (27.4V DC nominal at 20°C)
24V DC, 1.0A suitable for either Metron or Solenoid
3x rated at 1A each programmable
4x rated at 1A 30VAC/DC (max) 10mA 5V (min) [2x Fixed – Fire / Fault, 2x Programmable]
8x rated at 1A 30VAC/DC (max) 10mA 5V (min) programmable (requires EXP-008)
External Inputs (Monitored)
7x Fixed (Mode, Manual Trigger, Hold, Abort, Flow Monitor, Valve Monitor, Pressure Monitor)
4x Programmable
RS485 to Remote Status Indicators
100 Fire / Trigger Events, 500 General Log Events
EN12094-1:2003, EN12094-3 :2003,
EN54-2:1997 +A1:2006, EN54-4:1997 +A1:2002 +A2:2006, EN54-13 :2005
As our policy is one of constant product improvement the right is therefore reserved to modify product specifications without prior notice
The overall capability of the power supply is restricted to panel loading and maximum power available from the AUX outputs. Refer to the
relevant sections of this manual for the minimum and maximum output voltages of each circuit.
The charger is turned off in alarm.