3.3.7 General Options
The display presents a menu of user general options.
The Level 2 Time Out can be configured in the range 0 – 5
minutes (0 = No time out – stay in Level 2)
After the timeout, the menu functions and user controls are
inhibited. Password entry is required to re-enable these.
Determines if the panel shall report earth detection faults.
Determines the normal, quiescent state of the contacts
associated with the equipment used to sense loss of
extinguishant pressure (applies to all system inputs used
for pressure loss detection).
Normally Open /
Normally Closed
Shows the checksum of the configuration memory.
Option to erase the configuration (press the button).
Shows the current program version
Press the button to show the program checksum.
Determines the information that is recorded in the log.
Standard+ Mode also records the return to normal
transitions.
Determines the telephone contact number that is shown
on the normal display when there is an acknowledged fault
condition.
Determines the date/time at which a fault warning
messages will be displayed to indicate service is overdue.
Determines if the panel permits the buzzer to be muted at
Level 1 or if it can only be muted at Level 2.
Determines if the user is presented with the choice of
resetting ‘gas only’ or ‘fire & gas’ on a reset , alternativley
no menu is presented and ‘fire & gas’ are always reset.
Used to turn on/ off daylight saving mode – which
automatically shifts the current time forward/ backwards by
1 hour on programmed days of the year.
Determines if the panel shall annunciate a total loss of
power.
Reset from the fire alarm condition.
For full compliance with both EN54-2 and EN12094-1 the ‘PROMPT’ option
must be selected for Reset Mode. For compliance with only 12094-1 select the
‘ALL’ option. This option provides a single reset button action to reset the
system (note reset is inhibited during the activation condition).
3.3.7.1 Daylight Saving Options
The display presents a menu of the daylight saving configuration.
Determines whether the daylight saving function is on or
off. On means that the time will be shifted forwards &
backwards by 1 hour, two times a year on the dates
determined below.
Specifies which occurance of the day specified (below) in
the month specified (below) the time will be shifted
forwards by 1 hour (at 2AM the time will change to 3AM).
Specifies on which day of the week the time will be shifted
forwards by 1 hour.