Chapter 6
Planning Your Application Program
$aaSiER
Name Initialize EEPROM Data
Description Initializes all EEPROM data in a specified analog in-
put module to their default values. This command is
sent following a failed attempt to calibrate a module
(the module shows no effect from an attempted cali-
bration). Following initialization, the problem
module should readily accept calibration.
Syntax $aaSiER(cr)
$ is a delimiter character.
aa (range 00-FF) represents the 2-character hexadeci-
mal Modbus network address of the ADAM-5000/
TCP system. Si identifies the I/O slot in which you
wish to initial- ize all EEPROM data. ER represents
the initialize EEPROM data command.
(cr) is the terminating character, carriage return (0Dh)
Response !aa(cr) if the command is valid.
?aa(cr) if an invalid operation was entered.
There is no response if the module detects a syntax
error or communication error or if the specified ad-
dress does not exist.
! delimiter character indicating a valid command was
received.
? delimiter character indicating the command was
invalid.
aa (range 00-FF) represents the 2-character hexadeci-
mal Modbus network address of an ADAM-5000/
TCP system.
(cr) is the terminating character, carriage return (0Dh)
6-56 ADAM-5000/TCP User’s Manual

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Advantech ADAM-5000L/TCP and is the answer not in the manual?

Advantech ADAM-5000L/TCP Specifications

General IconGeneral
BrandAdvantech
ModelADAM-5000L/TCP
CategoryI/O Systems
LanguageEnglish

Related product manuals