Planning Your Application Program
Chapter 6
Example command: $01S0C1ALEE(cr)
response: !01(cr)
Channel 1 of slot 0 in the ADAM-5000/TCP system
at address 01h is instructed to enable its Low alarm
function. The module confirms that its Low alarm
function has been enabled.
Note: An analog input module requires a maximum of 2 seconds after
it receives an Enable/Disable Alarm command to let the setting
take effect. During this interval, the module cannot be addressed
to perform any other actions.