EasyManua.ls Logo

Advantech ADAM-5000L/TCP

Advantech ADAM-5000L/TCP
341 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Planning Your Application Program
$aaSiCjAh
Name Read Alarm Mode
Chapter 6
Description Returns the alarm mode for the specified channel in
the specified ADAM-5000/TCP system.
Syntax $aaSiCjAh(cr)
$ is a delimiter character.
aa (range 00-FF) represents the 2-character hexadeci-
mal Modbus network address of an ADAM-5000/
TCP system.
SiCj identifies the desired slot i (i : 0 to 7) and the
desired channel j (j : 0 to 7). Ah is the Read Alarm
Mode command.
h indicates alarm type and can have the value H =
High alarm, L = Low alarm
(cr) represents terminating character, carriage return
(0Dh)
Response !aas(cr) if the command was valid There is no
response if the system detects a syntax error or
communication error or if the specified ad- dress
does not exist.
! delimiter character indicating a valid command was
received.
aa represents the 2-character hexadecimal address
of the corresponding ADAM-5000/TCP system.
s indicates alarm mode and can have the value M =
Momentary mode, L = Latching mode
(cr) represents terminating character, carriage return
(0Dh)
ADAM-5000/TCP User’s Manual
6-111

Table of Contents

Related product manuals