Planning Your Application Program
$aaSiCjCh
Name Clear Latch Alarm
Chapter 6
Description Sets the High/Low alarm to OFF (no alarm) for the
specified input channel in the addressed
ADAM-
5000/TCP system
Syntax $aaSiCjCh(cr)
$ is a delimiter character.
aa (range 00-FF) represents the 2-character hexadeci-
mal Modbus network address of an ADAM-5000/
TCP system.
SiCj identifies the desired slot i (i : 0 to 7) and the
desired channel j (j : 0 to 7). Ch is the Clear Latch
Alarm command.
h indicates alarm type and can have the value H =
High alarm, L = Low alarm
(cr) represents terminating character, carriage return
(0Dh)
Response !aa(cr) if the command was valid There is no
response if the system detects a syntax error or
communication error or if the specified ad- dress
does not exist.
! delimiter character indicating a valid command was
received.
aa represents the 2-character hexadecimal Modbus
network address of the corresponding ADAM-5000
system.
(cr) represents terminating character, carriage return
(0Dh)
ADAM-5000/TCP User’s Manual