Chapter 6
Planning Your Application Program
#aaSi
Name Read All Channel Counter (Frequency) Data
Description Return the input value of all channels for the speci-
fied input module for a specified system in engineer-
ing unit only.
Syntax #aaSi(cr)
# is a delimiter character.
aa (range 00-FF) represents the 2-character hexadeci-
mal Modbus network address of the ADAM-5000/
TCP system you want to interrogate. Si is the I/O
slot of ADAM-5000 system you want to read.
(cr) is the terminating character, carriage return (0Dh)
Response >(data) (data) (data) (data) (cr) if the command is valid.
?aa (cr) if an invalid operation was entered. There
is no response if the module detects a syntax error
or communication error or if the specified ad- dress
does not exists.
> is a delimiter character.
? is a delimiter character indicating the command
being invalid.
(data) is the input value in engineering units of the
interrogated module of the specified system. If the
numbers of (data) are ten ,counter/frequency mode
is in decimal format. If the numbers of (data) are eight,
counter/frequency mode is in hexadecimal format. If
(data) = “ “, it means the channel is invalid.
(cr) is the terminating character, carriage return (0Dh).
6-154 ADAM-5000/TCP User’s Manual

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Advantech ADAM-5000L/TCP and is the answer not in the manual?

Advantech ADAM-5000L/TCP Specifications

General IconGeneral
BrandAdvantech
ModelADAM-5000L/TCP
CategoryI/O Systems
LanguageEnglish

Related product manuals