Planning Your Application Program
Chapter 6
$aaSi0(data)
Name Set Digital filter Scale
Description Set the filter seconds to start to measure the input
signal.
Syntax $aaSi0(data)(cr)
$ is a delimiter character.
aa (range 00-FF) represents the 2-character hexadeci-
mal address of the ADAM-5000/TCP system which
is to be calibrate.
Si identifies the specified slot.
0 is the command for setting digital filter scale.
(data)
represents filter seconds from 8µs~65000 µs.
Be aware that (data) has 5 characters.
(cr) is the terminating character, carriage return (0Dh)
Response !aa(cr) if the command is valid.
?aa(cr) if an invalid operation was entered. There is
no response if the module detects a syntax error or
communication error or if the specified ad- dress
does not exists.
! delimiter character indicating a valid command was
received.
? delimiter character indicating the command was in-
valid.
aa (range 00-FF) represents the 2-character hexadeci-
mal address of an ADAM-5000/TCP system.
(cr) is the terminating character, carriage return (0Dh)
Example command: $01S3000765(cr)
response: !01(cr)
The ADAM-5080 in slot 3 of the ADAM-5000/TCP
system at address 01h needs 765m seconds to start
to measure the input.
ADAM-5000/TCP User’s Manual
6-159

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Advantech ADAM-5000L/TCP and is the answer not in the manual?

Advantech ADAM-5000L/TCP Specifications

General IconGeneral
BrandAdvantech
ModelADAM-5000L/TCP
CategoryI/O Systems
LanguageEnglish

Related product manuals