Planning Your Application Program
$aaSiCjCh
Name Clear Alarm Status
Description Returns the alarm status to normal
Chapter 6
Syntax $aaSiCjCh(cr)
$ is a delimiter character.
aa (range 00-FF) represents the 2-character hexadeci-
mal Modbus network address of an ADAM-5000/
TCP system. SiCj identifies the desired slot i and the
desired chan- nel j.
C is the clear Alarm Mode command. h indicates
alarm type and can have the value H = High alarm,
L = Low alarm
(cr) represents terminating character, carriage return
(0Dh)
Response !aa(cr) if the command was valid There is no
response if the system detects a syntax error or
communication error or if the specified ad- dress
does not exist.
! delimiter character indicating a valid command was
received.
aa represents the 2-character hexadecimal Modbus
network address of the corresponding ADAM-5000/
TCP system.
(cr) represents terminating character, carriage return
(0Dh)
ADAM-5000/TCP User’s Manual
6-175