3 Installation
UPS IST7 (10KVA-40KVA)
User Manual
22
Type 10KVA 15KVA 20KVA
33
mode
31
mode
11
mode
33
mode
31
mode
11
mode
33
mode
31
mode
11
mode
Bypass input (A) 19.5 58.6 58.6 27.5 82.5 82.5 35.5 106.4 106.4
DC input (A) 54.8 54.8 54.8 41.1 41.1 41.1 54.8 54.8 54.8
AC output (A) 15.2 45.6 45.6 22.7 68.2 68.2 30.3 90.9 90.9
UPS max. steady state phase current
Type 30KVA 40KVA
33 mode 31 mode 33 mode 31 mode
AC input (A) 65.7 65.7 81.7 81.7
Bypass input (A) 65.7 197.1 81.7 245.0
DC input (A) 82.2 82.2 109.6 109.6
AC output (A) 45.5 136.4 60.6 181.8
3.2.4 Select Input Breaker
We suggest to add a breaker (we suggest to select the breaker with feedback double pole
disconnection equipment) that matches the UPS power at the front of the UPS input to
insulate the mains. Considering the UPS charge power and the impact current while power
on, the selected breaker must be 1.5 to 2 times of UPS input max. current, and cannot with
leakage protection, which is to avoid wrong action of breaker. The breaker of DC input should
be select more than the 250V DC.
Recommended input breaker list
Type 10KVA 15KVA 20KVA
33
mode
31
mode
11
mode
33
mode
31
mode
11
mode
33
mode
31
mode
11
mode
AC input
(A)
32*3P 32*3P 80*1P 63*3P 63*3P
100*3
P
63*3P 63*3P
150*3
P