UPS IST7 (10KVA-40KVA)
User Manual 3 Installation
23
Type 10KVA 15KVA 20KVA
33
mode
31
mode
11
mode
33
mode
31
mode
11
mode
33
mode
31
mode
11
mode
Bypass
input (A)
32*3P 80*1P 80*1P 63*3P
100*3
P
100*3
P
63*3P
100*3
P
150*3
P
DC input
(A)
100*3
P
100*3
P
100*3
P
63*3P 63*3P 63*3P
100*3
P
100*3
P
100*3
P
AC output
(A)
32*3P 80*1P 80*1P 63*3P
100*3
P
100*3
P
63*3P
100*3
P
100*3
P
Recommended input breaker list
Type 30KVA 40KVA
33 mode 31 mode 33 mode 31 mode
AC input (A) 100*3P 100*3P 100*3P 100*3P
Bypass input (A) 100*3P 250*1P 100*3P 300*1P
DC input (A) 125*3P 125*3P 175*3P 175*3P
AC output (A) 100*3P 200*1P 100*3P 250*1P
3.2.5 Select Wires
The cross-sectional area of the following cable is only for reference when the user is
connected wire for a length of about 5 meters. If the length of the lead wire exceeds 20 meters,
the cross-sectional area of the conductor wire shall be increased.
Recommended cross-sectional area of wire (unit: mm
2
, environment temperature: 25)
33 mode
10KVA 15KVA 20KVA 30KVA 40KVA
Mains input live wire
(U/V/W)
4 6 6 16 16