54
Charge set page 2 of battery management
Setting description for battery mange page
Item Settable value
Battery type Lead-acid
Battery capacity (Ah) 1~2000
Battery amount (Cell) 48-120
Battery static function On, Off
Battery static time (day) 1~30
Battery static delay time (h) 1~48
Battery backup function On, Off
Single battery low-voltage protection (V/Cell) 1.667~1.867
Single battery test ending voltage (V/Cell) 1.667~1.867
Equalizing charge voltage of single battery
(V/Cell)
2.083~2.417
Floating charge voltage of single battery
(V/Cell)
2.083~2.333
Temperature compensation On, Off