Benchmark 2.0 LN Installation, Operation & Maintenance Manual
APPENDIX E – BOILER DEFAULT SETTINGS
Page 132 of 168 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0046_0J
06/18/2015 Phone: 800-526-0288 GF-123
Table E-1: Boiler Default Settings (Continued)
MENU & OPTION FACTORY DEFAULT
Configuration Menu - Continued
Pump Delay Timer 0 min
Aux Start On Dly 0 sec
Failsafe Mode Shutdown
Analog Output
Valve Position 0-10V
CAUTION:
Change
Low Fire Timer 2 sec
Setpt Limiting Disabled
Setpt Limit Band (If Setpt Limiting = Enabled) 5°F
Network Timeout 30 seconds
Hi DB Setpt En 30
Demand Offset 10
Deadband High 2
Deadband Low 2
Spark Monitor Disabled
Spark Current 0
Tuning Menu
Prop Band 70°F
Integral Gain 1.00
Derivative Time 0.00 min
Warmup Prop Band 95
Warmup Int Gain 50
Warmup PID Timer 20
Reset Defaults No