Benchmark 2.0 LN Installation, Operation & Maintenance Manual
APPENDIX E – BOILER DEFAULT SETTINGS
OMM-0046_0J AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 131 of 168
GF-123 Ph.: 800-526-0288 06/18/2015
APPENDIX E – BOILER DEFAULT SETTINGS
Table E-1: Boiler Default Settings
MENU & OPTION FACTORY DEFAULT
Setup Menu
Password 0
Language English
Unit of Temp Fahrenheit
Comm Address 0
Baud Rate 9600
Configuration Menu
Internal Setpt 130°F
Unit Type BMK Boiler LN
Unit Size 2000 MBH (2.0 MBTU)
Fuel Type Natural Gas
Boiler Mode Constant Setpoint
Remote Signal
(If Mode = Remote Setpoint, Direct Drive or
Combination)
4 – 20 mA / 1-5V
Bldg Ref Temp
(If Boiler Mode = Outdoor Reset)
70°F
Reset Ratio
(If Boiler Mode = Outdoor Reset)
1.2
Outdoor Sensor Disabled
System Start Tmp
(If Outdoor Sensor = Enabled)
60°F
Setpt Lo Limit 60°F
Setpt Hi Limit 195°F
Temp Hi Limit 195°F
Max Valve Position 100%