18.14 TYPE OF GAS MONITOR
R1234ze
Gas Type
Type of refrigerant gas.
18.15 ELECTRONIC VALVE NUMBER MONITOR
2
Number EEV
Number of electronic valves present.
18.16 GLYCOL WATER TEMPERATURE AND ENABLING
MONITOR
00.0 °C
N
Glycolated water
management
Glycolated water
freezing temp.
Glycol water management enabling.
Water-glycol mixture freezing temperature (TCMA).
When the function is enabled, the following parameters are calculated automatical-
ly and cannot be changed:
— minimum limit of the cooling setpoint (TCMA + 4°C)
— antifreeze prevention setpoint (TCMA + 3.8°C)
— antifreeze alarm setpoint (TCMA + 3°C)
— antifreeze heater activation setpoint (TCMA + 3.5°C)
— cooling force-o setpoint (TCMA + 3.5°C)
18.17 BMS PARAMETERS MONITOR
Modbus
(BMS)
001
19200
supervisor
Address
Baudrate
Protocol
— Serial address 1 for supervisor
— Speed of communication
— Type of protocol used for communication with the supervisor: Lon, pCOweb,
Modbus
18.18 BMS2 PARAMETERS MONITOR
Modbus
(BMS2)
001
19200
supervisor
Address
Baudrate
Protocol
— Serial address 2 for supervisor
— Speed of communication
18.19 MULTIFUNCTION INPUT MONITOR
NTC
Probe 7 cong.
Function
Type
None
Multifunction input (MASTER ONLY) on input B7 active on master.
Function:
— None: no functionality
— Setpoint: working setpoint selection
— Limit: limitation of the cooling capacity
— Demand: Cooling capacity request
— Comp.Ext: Setpoint compensation with temperature
Type:
— NTC: input with temperature and probe NTC10K
— 0-10V: input 0-10 volt dc
— 4-20mA: Input 4-20mA