7
2 HOME MENU
HOME
02/12/21
14:58:39
WFGI2101°°ZL°°°°
1
11.5 °C
11.2 °C
44.4 °C
40.4 °C
0 0
11.4 bar
2.8 bar
O by Keyboard
Pow
Req
This mask displays:
1. General unit status:
— Current date and time
— Machine model;
— Control card whose parameters are displayed (pCO5+)
— Condenser inlet temperature (CN);
— Condenser outlet temperature (CN);
— High, low pressure and compressor status;
— Electronic valve status;
— Request and power output;
— Evaporator (EV) input temperature;
— Evaporator (EV) output temperature;
2. The machine operating status:
— ON: machine on
— PUMPDOWN: pumpdown cycle in progress
— OFF BY KEY: machine turned o by the keypad command
— OFF BY DIG. IN.: machine turned o by remote contact
— OFF BY SUPERVISOR.: machine turned o by supervisor
— OFF BY TIME BAND: machine turned o by the timer
— OFF BY ALARM: machine turned o by alarm
— OFF BY SER.OFFL: machine turned o due to failure of adjustment probe from
supervisor
Depending on the number of compressors and the position of the adjustment
probe, the Home page can appear dierently.
— 2 compressors, Master adjustment probe:
HOME
02/12/21
09:50:23
WFGI2502°°ZL°°°°
1
11.6 °C
11.2 °C
0 0
11.4 bar
2.8 bar
11.4 bar
2.8 bar
45.0 °C
40.4 °C
44. 4 °C
O by Keyboard
Pow
Req
— 2 compressors, common adjustment probe:
HOME
03/12/21
09:54:33
WFGI2502°°ZL°°°°
1
11.6 °C
11.2 °C
0 0
11.4 bar
2.8 bar
11.4 bar
2.8 bar
40.4 °C
40.0 °C
O by Keyboard
Pow
Req
— 3 compressors, Master adjustment probe:
HOME
03/12/21
10:00:35
WFGI7203°°ZL°°°°
1
11.6 °C
11.2 °C
0 0
11.4 bar
2.8 bar
11.4 bar
2.8 bar
11.4 bar
2.8 bar
40.4 °C
45.0 °C
45.0 °C
44.4 °C
O by Keyboard
Pow
Req

Table of Contents