EasyManua.ls Logo

AERMEC PGD1 - Page 42

AERMEC PGD1
46 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
42
Code Description Note Type
AL094
EVD - LOP 2 alarm 2
AL095
EVD - MOP 2 alarm 2
AL096
EVD - Low overheating 2 2
AL097
EVD - Low suction temperature 2 2
AL100
Inverter – envelop init error The compressor is working out of envelope 3
AL101
Inverter – fault 3
AL102
Inverter – overcurrent 3
AL103
Inverter - over voltage 3
AL104
Inverter – over temperature
 inverter temperature too high
 check the liquid valve and/or refrigerant load. The valve activates
when the oil exceeds 100°C and deactivates when it goes below
95°C
3
AL105
Inverter – under voltage 3
AL106
Inverter – power supply fault  failure of a phase or imbalance between phases 3
AL107
Inverter – hardware fault 3
AL108
Inverter – temperature sensor fault
 inverter temperature sensor fault. Check the oil sensor and motor
sensor
3
AL109
Inverter – hardware conguration error incorrect hardware conguration 3
AL110
Inverter – conguration data error  incorrect software conguration 3
AL111
Inverter – conguration parameter error  incorrect inverter parameters 3
AL112
Inverter – motor thermal overload  motor winding temperature above limits 3
AL113
Inverter – motor overload 3
AL115
Inverter – motor phase failed 3
AL116
Inverter – high oil temperature
 high oil temperature (check oil heater)
 warning if greater than 115°C
 fault if greater than 120°C
 reset alarm if less than 105°C
3
AL117
Inverter – low oil temperature 3
AL118
Inverter - Compressor Short Cycling
 compressor starting is requested before the minimum time
between two starts has passed. This occurs only at the Warning level
3
AL119
Inverter – envelope error The compressor is working out of envelope 3
AL120
Inverter – serial control timeout  power request from card pCO5+ to inverter timeout 3
AL121
Inverter – communication error 3
AL122
Inverter – datalog error 3
AL123
Inverter – pressure sensor fault 3
The alarms read by the compressor inverter card can have three levels, as indicated in the example window:
Inverter
AL: XXX U:01
(Warning/Critical/Fault)
ALARM NAME
Warning: pre-alarm condition
Critical: becomes Fault after 30’
Fault: compressor OFF manual reset alarm

Table of Contents

Related product manuals