Technical Data - Direct Expansion
Performance Data - Single Compressor (X1)
Full Load (X1)
Ambient (°C)
Unit
Air On DB / RH 25 30 35 40 46
LIR6042U-X123-0
25°C / 42%
Gross Total Cooling (kW)
18.83 18.83 21.14 20.33 20.50
Power Input (kW)
4.43 4.43 6.19 6.84 9.53
EER
4.25 4.25 3.42 2.97 2.15
30°C / 32%
Gross Total Cooling (kW)
26.86 26.62 29.28 28.21 28.62
Power Input (kW)
6.79 7.02 9.67 10.68 14.59
EER
3.95 3.79 3.03 2.64 1.96
35°C / 24%
Gross Total Cooling (kW)
33.93 35.35 34.24 33.05 30.55
Power Input (kW)
8.16 10.80 11.98 13.23 14.66
EER
4.16 3.27 2.86 2.50 2.08
40°C / 18%
Gross Total Cooling (kW)
39.69 38.63 36.19 35.02 32.20
Power Input (kW)
9.84 10.98 12.05 13.29 14.70
EER
4.03 3.52 3.00 2.63 2.19
LIR6042U-X130-0
25°C / 42%
Gross Total Cooling (kW)
22.72 24.17 23.32 22.40 21.23
Power Input (kW)
5.80 7.17 7.92 8.74 9.78
EER
3.92 3.37 2.94 2.56 2.17
30°C / 32%
Gross Total Cooling (kW)
32.40 33.97 32.81 31.57 29.98
Power Input (kW)
8.38 10.93 12.11 13.34 14.88
EER
3.87 3.11 2.71 2.37 2.01
35°C / 24%
Gross Total Cooling (kW)
38.48 37.37 35.21 33.05 30.55
Power Input (kW)
9.98 11.11 12.16 13.26 14.66
EER
3.86 3.36 2.90 2.49 2.08
40°C / 18%
Gross Total Cooling (kW)
40.98 38.63 36.19 35.02 32.20
Power Input (kW)
10.01 11.01 12.05 13.30 14.69
EER
4.09 3.51 3.00 2.63 2.19
Note: The shaded area indicates that the Compressor speed is modulated to achieve dew point control.
All the performance data is based on a SHR of 1.0.
Maximum duty data is based on achievable duty at maximum air volume
Performance data is based upon a unit with no ltration.