Water Temperatures (°C)
Air On DB (°C)/RH (%) 10/16 11/17 12/18 13/19 14/20
LIR6042U-CC22
25 / 42
Gross Total Cooling (kW)
12.65 11.40 10.16 8.92 7.68
Power Input (kW)
0.33 0.33 0.33 0.33 0.33
EER
38.33 34.55 30.79 27.03 23.27
30 / 32
Gross Total Cooling (kW)
19.47 18.21 16.95 15.68 14.39
Power Input (kW)
0.33 0.33 0.33 0.33 0.33
EER
59.00 55.18 51.36 47.52 43.61
35 / 24
Gross Total Cooling (kW)
25.82 24.58 23.35 22.11 20.88
Power Input (kW)
0.33 0.33 0.33 0.33 0.33
EER
78.24 74.48 70.76 67.00 63.27
40 / 18
Gross Total Cooling (kW)
31.84 30.62 29.40 28.19 26.97
Power Input (kW)
0.33 0.33 0.33 0.33 0.33
EER
96.48 92.79 89.09 85.42 81.73
LIR6042U-CC26
25 / 42
Gross Total Cooling (kW)
15.33 13.72 12.14 10.61 9.16
Power Input (kW)
0.67 0.67 0.67 0.67 0.67
EER
22.88 20.48 18.12 15.84 13.67
30 / 32
Gross Total Cooling (kW)
23.66 22.13 20.59 19.05 17.50
Power Input (kW)
0.67 0.67 0.67 0.67 0.67
EER
35.31 33.03 30.73 28.43 26.12
35 / 24
Gross Total Cooling (kW)
31.40 29.89 28.38 26.87 25.37
Power Input (kW)
0.67 0.67 0.67 0.67 0.67
EER
46.87 44.61 42.36 40.10 37.87
40 / 18
Gross Total Cooling (kW)
38.80 37.30 35.80 34.31 32.82
Power Input (kW)
0.67 0.67 0.67 0.67 0.67
EER
57.91 55.67 53.43 51.21 48.99
IMPORTANT
Cooling capacity is based upon each coil running independently. If the unit is used with both circuits operating the
second circuit will have reduced capacity due to the lower air on temperature (equal to the air off temperature of the rst
coil).