Technical Data - Dual Circuit Chilled Water
Performance Data - (CC)
Full Load - (CC)
LogiCool InRak™
IT Cooling
44
InRak™ Technical Manual 7462807 V1.11.0_04_2016
TechnicalDual Circuit
(CC)
Water Temperatures (°C)
Air On DB (°C)/RH (%) 10/16 11/17 12/18 13/19 14/20
LIR6042U-CC30
25 / 42
Gross Total Cooling (kW)
16.49 14.73 13.01 11.35 9.81
Power Input (kW)
0.96 0.96 0.96 0.96 0.96
EER
17.18 15.34 13.55 11.82 10.22
30 / 32
Gross Total Cooling (kW)
25.39 23.75 22.10 20.44 18.77
Power Input (kW)
0.96 0.96 0.96 0.96 0.96
EER
26.45 24.74 23.02 21.29 19.55
35 / 24
Gross Total Cooling (kW)
33.72 32.10 30.47 28.85 27.23
Power Input (kW)
0.96 0.96 0.96 0.96 0.96
EER
35.13 33.44 31.74 30.05 28.36
40 / 18
Gross Total Cooling (kW)
41.69 40.08 38.47 36.86 35.25
Power Input (kW)
0.96 0.96 0.96 0.96 0.96
EER
43.43 41.75 40.07 38.40 36.72
LIR6042U-CC40
25 / 42
Gross Total Cooling (kW)
19.94 17.80 15.70 13.73 11.94
Power Input (kW)
2.11 2.11 2.11 2.11 2.11
EER
9.45 8.44 7.44 6.51 5.66
30 / 32
Gross Total Cooling (kW)
30.61 28.62 26.62 24.62 22.60
Power Input (kW)
2.11 2.11 2.11 2.11 2.11
EER
14.51 13.56 12.62 11.67 10.71
35 / 24
Gross Total Cooling (kW)
40.75 38.78 36.80 34.82 32.84
Power Input (kW)
2.11 2.11 2.11 2.11 2.11
EER
19.31 18.38 17.44 16.50 15.56
40 / 18
Gross Total Cooling (kW)
50.49 48.53 46.57 44.60 42.65
Power Input (kW)
2.11 2.11 2.11 2.11 2.11
EER
23.93 23.00 22.07 21.14 20.21