Technical Data - Dual Circuit Chilled Water
Performance Data - (CC)
Part Load - (CC)
Water Temperatures (°C)
Air On DB (°C) / RH (%) 10/16 11/17 12/18 13/19 14/20
LIR6042U-CC22
25 / 42
Gross Total Cooling (kW) 8.24 7.62 6.96 6.23 5.39
Power Input (kW) 0.09 0.09 0.09 0.09 0.09
EER 91.56 84.67 77.33 69.22 59.89
30 / 32
Gross Total Cooling (kW) 12.35 11.55 10.74 9.92 9.08
Power Input (kW) 0.09 0.09 0.09 0.09 0.09
EER 137.22 128.33 119.33 110.22 100.89
35 / 24
Gross Total Cooling (kW) 16.37 15.61 14.84 14.06 13.28
Power Input (kW) 0.09 0.09 0.09 0.09 0.09
EER 181.89 173.44 164.89 156.22 147.56
40 / 18
Gross Total Cooling (kW) 20.13 19.37 18.62 17.86 17.11
Power Input (kW) 0.09 0.09 0.09 0.09 0.09
EER 223.67 215.22 206.89 198.44 190.11
LIR6042U-CC26
25 / 42
Gross Total Cooling (kW) 9.44 8.64 7.82 6.95 6.00
Power Input (kW) 0.13 0.13 0.13 0.13 0.13
EER 72.62 66.46 60.15 53.46 46.15
30 / 32
Gross Total Cooling (kW) 14.30 13.38 12.44 11.50 10.54
Power Input (kW) 0.13 0.13 0.13 0.13 0.13
EER 110.00 102.92 95.69 88.46 81.08
35 / 24
Gross Total Cooling (kW) 18.96 18.06 17.17 16.27 15.36
Power Input (kW) 0.13 0.13 0.13 0.13 0.13
EER 145.85 138.92 132.08 125.15 118.15
40 / 18
Gross Total Cooling (kW) 23.33 22.45 21.57 20.69 19.80
Power Input (kW) 0.13 0.13 0.13 0.13 0.13
EER 179.46 172.69 165.92 159.15 152.31
IT Cooling
LogiCool InRak™
45
InRak™ Technical Manual 7462807 V1.11.0_04_2016
Technical Dual Circuit
(CC)
IMPORTANT
Cooling capacity is based upon per coil running independent of each other. If the unit is used with both circuits operating
the second circuit will have reduced capacity due to the lower air on temperature.