Technical Data - Chilled Water
Performance Data - (C0)
Full Load - (C0)
Water Temperatures (°C)
Air On DB / RH 10/16 11/17 12/18 13/19 14/20
LIR6042U-C030
25°C / 42%
Gross Total Cooling (kW)
20.28 18.67 17.20 15.54 13.34
Power Input (kW)
0.36 0.36 0.36 0.36 0.36
EER
56.33 51.86 47.78 43.17 37.06
30°C / 32%
Gross Total Cooling (kW)
29.01 27.44 26.05 24.48 22.35
Power Input (kW)
0.36 0.36 0.36 0.36 0.36
EER
80.58 76.22 72.36 68.00 62.08
35°C / 24%
Gross Total Cooling (kW)
37.04 35.58 34.27 32.74 30.59
Power Input (kW)
0.36 0.36 0.36 0.36 0.36
EER
102.89 98.83 95.19 90.94 84.97
40°C / 18%
Gross Total Cooling (kW)
44.61 43.28 42.13 40.65 38.31
Power Input (kW)
0.36 0.36 0.36 0.36 0.36
EER
123.92 120.22 117.03 112.92 106.42
LIR6042U-C040
25°C / 42%
Gross Total Cooling (kW)
24.56 22.58 20.70 18.59 15.93
Power Input (kW)
0.65 0.65 0.65 0.65 0.65
EER
37.78 34.74 31.85 28.60 24.51
30°C / 32%
Gross Total Cooling (kW)
34.89 33.04 31.35 29.44 26.91
Power Input (kW)
0.65 0.65 0.65 0.65 0.65
EER
53.68 50.83 48.23 45.29 41.40
35°C / 24%
Gross Total Cooling (kW)
44.87 43.02 41.32 39.42 36.97
Power Input (kW)
0.65 0.65 0.65 0.65 0.65
EER
69.03 66.18 63.57 60.65 56.88
40°C / 18%
Gross Total Cooling (kW)
54.12 52.43 50.89 49.04 46.43
Power Input (kW)
0.65 0.65 0.65 0.65 0.65
EER
83.26 80.66 78.29 75.45 71.43
All the performance data is based on a SHR of 1.0.
Maximum duty data is based on achievable duty at maximum air volume.
Performance data is based upon a unit with no ltration.