Technical Data - Chilled Water
Performance Data - (C0)
Full Load - (C0)
Water Temperatures (°C)
Air On DB / RH 10/16 11/17 12/18 13/19 14/20
LIR6042U-C045
25°C / 42%
Gross Total Cooling (kW)
24.53 22.28 20.11 18.02 16.00
Power Input (kW)
0.97 0.97 0.97 0.97 0.97
EER
25.29 22.97 20.73 18.58 16.49
30°C / 32%
Gross Total Cooling (kW)
36.59 34.45 32.33 30.07 27.52
Power Input (kW)
0.97 0.97 0.97 0.97 0.97
EER
37.72 35.52 33.33 31.00 28.37
35°C / 24%
Gross Total Cooling (kW)
47.81 45.67 43.53 41.34 39.03
Power Input (kW)
0.97 0.97 0.97 0.97 0.97
EER
49.29 47.08 44.88 42.62 40.24
40°C / 18%
Gross Total Cooling (kW)
58.37 56.24 54.11 51.95 49.71
Power Input (kW)
0.97 0.97 0.97 0.97 0.97
EER
60.18 57.98 55.78 53.56 51.25
LIR6042U-C060
25°C / 42%
Gross Total Cooling (kW)
30.71 27.74 24.82 21.98 19.29
Power Input (kW)
1.88 1.88 1.88 1.88 1.88
EER
16.34 14.76 13.20 11.69 10.26
30°C / 32%
Gross Total Cooling (kW)
45.69 42.78 39.85 37.02 34.41
Power Input (kW)
1.88 1.88 1.88 1.88 1.88
EER
24.30 22.76 21.20 19.69 18.30
35°C / 24%
Gross Total Cooling (kW)
59.57 56.76 53.94 51.17 48.49
Power Input (kW)
1.88 1.88 1.88 1.88 1.88
EER
31.69 30.19 28.69 27.22 25.79
40°C / 18%
Gross Total Cooling (kW)
72.78 70.00 67.22 64.49 61.84
Power Input (kW)
1.88 1.88 1.88 1.88 1.88
EER
38.71 37.23 35.76 34.30 32.89
IT Cooling
LogiCool InRak™
35
InRak™ Technical Manual 7462807 V1.11.0_04_2016
Technical
Single Circuit
(C0)
All the performance data is based on a SHR of 1.0.
Maximum duty data is based on achievable duty at maximum air volume.
Performance data is based upon a unit with no ltration.