Technical - Direct Expansion
Performance Data - Single Compressor (X1)
Max EER (X1)
Ambient (°C)
Unit
Air On DB / RH 25 30 35 40 46
LIR6042U-X123-0
25°C / 42%
Gross Total Cooling (kW)
10.85 10.85 10.97 10.52 13.66
Power Input (kW)
2.15 2.15 2.27 2.58 4.43
EER
5.05 5.05 4.83 4.08 3.08
30°C / 32%
Gross Total Cooling (kW)
17.17 17.17 17.59 16.92 16.05
Power Input (kW)
3.16 3.16 3.52 3.94 4.46
EER
5.42 5.42 4.98 4.28 3.59
35°C / 24%
Gross Total Cooling (kW)
17.89 17.89 18.56 19.43 18.24
Power Input (kW)
3.06 3.06 3.36 3.97 4.43
EER
5.85 5.85 5.52 4.89 4.12
40°C / 18%
Gross Total Cooling (kW)
23.29 24.70 26.78 20.34 19.64
Power Input (kW)
4.15 4.20 4.92 3.81 4.34
EER
5.61 5.88 5.44 5.34 4.53
LIR6042U-X130-0
25°C / 42%
Gross Total Cooling (kW)
15.02 15.02 14.75 14.16 13.41
Power Input (kW)
3.27 3.27 3.46 3.87 4.38
EER
4.59 4.59 4.26 3.67 3.07
30°C / 32%
Gross Total Cooling (kW)
17.17 22.81 17.26 16.63 15.81
Power Input (kW)
3.16 4.56 3.47 3.89 4.41
EER
5.43 5.00 4.97 4.28 3.59
35°C / 24%
Gross Total Cooling (kW)
23.21 23.21 18.56 19.09 18.24
Power Input (kW)
4.23 4.23 3.35 3.91 4.44
EER
5.49 5.49 5.54 4.88 4.12
40°C / 18%
Gross Total Cooling (kW)
23.29 24.70 26.78 20.34 19.64
Power Input (kW)
4.14 4.19 4.95 3.80 4.33
EER
5.63 5.89 5.41 5.35 4.54
All the performance data is based on a SHR of 1.0.
Max EER data is based on a part load condition (i.e. required duty of 50% of the maximum achievable duty of the unit).
Performance data is based upon a unit with no ltration.