40
a)
b)
c)
d)
e)
f) 82 % 82 % 84 % 90 %
g) 0,060 m³/s
216 m³/h
0,110 m³/s
396 m³/h
0,167 m³/s
600 m³/h
0,173 m³/s
623 m³/h
h) 0,06 kW 0,12 kW 0,11 kW 0,17 kW
i) 1040 W/(m³/s)
0,289 W/(m³/h)
1011 W/(m³/s)
0,281 W/(m³/h)
664 W/(m³/s)
0,184 W/(m³/h)
638 W/(m³/s)
0,177 W/(m³/h)
j) 1,0 m/s 0,8 m/s 1,0 m/s 1,0 m/s
k) 20 Pa 20 Pa 20 Pa 20 Pa
l) 201 Pa 195 Pa 111 Pa 137 Pa
m)
n) 37 % 40 % 39 % 38 %
o) 2 % @ 400 Pa
2 % @ 250 Pa
2 % @ 400 Pa
2 % @ 250 Pa
2 % @ 400 Pa
2 % @ 250 Pa
5 % @ 400 Pa
5 % @ 250 Pa
p)
q)
r) 40 dB(A) 40 dB(A) 40 dB(A) 40 dB(A)
s)
>67%/>73%
1641/1361 W/(m³/s)
>67%/>73%
1634/1354 W/(m³/s)
>67%/>73%
1686/1406 W/(m³/s)
>67%/>73%
1864/1584 W/(m³/s)
a)
b)
c)
d)
e)
f) 80 % 84 % 81 %
g) 0,264 m³/s
950 m³/h
0,264 m³/s
950 m³/h
0,290 m³/s
1044 m³/h
h) 0,23 kW 0,17 kW 0,36 kW
i) 771 W/(m³/s)
0,214 W/(m³/h)
491 W/(m³/s)
0,136 W/(m³/h)
638 W/(m³/s)
0,177 W/(m³/h)
j) 0,8 m/s 0,8 m/s 1,0 m/s
k) 20 Pa 20 Pa 100 Pa
l) 194 Pa 85 Pa 140 Pa
m)
n) 55 % 38 % 47 %
o) 2 % @ 400 Pa
2 % @ 250 Pa
2 % @ 400 Pa
2 % @ 250 Pa
2 % @ 400 Pa
2 % @ 250 Pa
p)
q)
r) 40 dB(A) 40 dB(A) 47 dB(A)
s)
>67%/>73%
1550/1270 W/(m³/s)
>67%/>73%
1670/1390 W/(m³/s)
>67%/>73%
1577/1297 W/(m³/s)
Product information according to “Commission Regulation (EU) No 1253/2014, Annex V - Information requirements for
NRVUs as referred to in Article 4(2)”.
Manufacturer Airmaster
Model AM 300 AM 500 AM 800 AM 900
Typology Non-residential ventilation unit / Bidirectional ventilation unit
Type of drive installed Variable speed drive (VSD)
Type of heat recovery system Recuperative heat exchanger / Counterow heat exchanger
Thermal eciency
Nominal ow rate
Electric power input
Internal specic fan power (SFP
int
)
Face velocity
Nominal external pressure (∆p
s, ext
)
Internal pressure drop of ventilation
components (∆p
s, int
)
Internal pressure drop of non-ventilation
components (∆p
s, add
)
Water Comfort Heater:
10 Pa
Water Comfort Heater:
10 Pa
Water Comfort Heater:
10 Pa
Water Comfort Heater:
10 Pa
Static eciency
of fans
Maximum external leakage rate
Maximum internal leakage rate
Energy performance of the lters 108 kWh/a, Class A+ 206 kWh/a, Class A+ 330 kWh/a, Class A+ 428 kWh/a, Class A+
Filter alarm signal See description in Operator’s Manual
Sound power level (L
WA
)
Disposal Se See description in Operator’s Manual, www.airmaster-as.com
Specic requirements 2016/2018
Thermal eciency
Internal specic fan power (SFP
int_limit
)
Manufacturer Airmaster
Model AM 1000 AM 1200 DV 1000
Typology Non-residential ventilation unit / Bidirectional ventilation unit
Type of drive installed Variable speed drive (VSD)
Type of heat recovery system Recuperative heat exchanger / Counterow heat exchanger
Thermal eciency
Nominal ow rate
Electric power input
Internal specic fan power (SFP
int
)
Face velocity
Nominal external pressure (∆p
s, ext
)
Internal pressure drop of ventilation
components (∆p
s, int
)
Internal pressure drop of non-ventilation
components (∆p
s, add
)
Water Comfort Heater:
10 Pa
Water Comfort Heater:
10 Pa
Undisclosed
Static eciency
of fans
Maximum external leakage rate
Maximum internal leakage rate
Energy performance of the lters 261 kWh/a, Class A+ 450 kWh/a, Class A+ 403 kWh/a, Class A+
Filter alarm signal Se See description in Operator’s Manual
Sound power level (L
WA
)
Disposal Se See description in Operator’s Manual, www.airmaster-as.com
Specic requirements 2016/2018
Thermal eciency
Internal specic fan power (SFP
int_limit
)