5–2 Using Block Transfer Messages
Understanding the Block 
Transfer Status Word
The block transfer status word is returned from the Remote I/O 
module. It is the first word associated with the rack in the controller 
input image table. This status word indicates the condition of the 
Remote I/O module itself and is not part of the standard block transfer 
instructions in the ladder program. Figure 5.1 details the individual 
bits. 
Figure 5.1 Remote I/O Status Word
Figure 5.2 Bit Timing
Reserved for future use.
Block Transfer Ready (BT_READY)
Block Transfer Write in Progress (BTW_IN_PROG)
Block Transfer Read Available (BTR_AVAIL)
Block Transfer Wait (BT_WAIT)
Block Transfer Error (BT_ERROR)
Block Transfer Write Available (BTW_AVAIL)
Reserved for future use.
Reserved for future use.
Bit 7
Bit 6
Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0Bit 17
Bit 16
Bit 15 Bit 14 Bit 13 Bit12  Bit 11 Bit 10
Status Description
Block Transfer 
Ready 
The SCANport product and Remote I/O module are communicating and are 
ready to process block transfers.
Block Transfer 
Write in 
Progress
A block transfer write is in progress between the controller and Remote I/O 
module. This bit is cleared when the data transfer to the module is complete.
Block Transfer 
Read Available
The Remote I/O module has data available for the controller to read. 
Block Transfer 
Wait
The Remote I/O module is communicating with the SCANport product. This 
bit is cleared when the data transfer between the module and SCANport 
product is complete.
Block Transfer 
Error
An error has occurred during communications with the SCANport product, or 
the BTW data is invalid.
Block Transfer 
Write Available
The Remote I/O module is ready to receive a Block Transfer Write.
BT Write Available
Status Bit 15
BTW
Request
BT Wait 
Status Bit 13
BTW data at 
Remote I/O Module
BT Read Data Available
Status Bit 12
BT Write In Progress
Status Bit 11
BTW
Complete
BTR 
Request