Configuring the Module 2–5
Setting Switches on SW3
Setting Block Transfer
SW 3.1 enables or disables block transfer. Enable block transfer if 
you are using messages (refer to Chapter 5) in your ladder logic 
program or if you are using DriveTools32 software. 
Important:
You cannot use both messages and DriveTools32 software 
at the same time. 
Block transfer uses the first module group (word) in the rack and 
group. 
Figure 2.3 Block Transfer Switch
To edit the block transfer setting, you need to:
1. Refer to the following table to determine the setting for SW 3.1:
2. Slide the switch to its appropriate position.
3. If Block Transfer is enabled, record “Block Transfer” in the first 
module group (word) of your I/O image table on page 2–4.
Settings take effect when a module or board first receives power. 
When you change a setting, you must remove and then reapply power 
for the new setting to take effect.
!
ATTENTION: Injury or equipment damage can result 
from loss of PLC or Controller Logic Commands (Stop, 
Start, etc.) when all these conditions are true:
• module firmware 3.04 or lower.
• 230.4k baud rate.
• block transfer is enabled (DIP switch SW3-1 is ON).
• block transfers to the module are used (in the ladder 
program or by DriveTools/DriveTools32 using a 
Remote I/O pass thru connection).
Do not use the 230.4k baud rate if you are using a module 
with 3.04 or earlier firmware and your program uses block 
transfers. Use the 57.6k or 115.2k baud rate instead.
Block Transfer SW 3.1
Disabled 0
Enabled 1
Off = 0
On = 1
Use SW 3.1 for setting the 
block transfer
Artisan Scientific - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisan-scientific.com