Programming
5-19
Advanced Setup Group (continued)
[Start Boost]
Parameter # 48 Factory Default See Table
0.37 kW
(0.5 HP)
0.55 kW
(0.75 HP)
0.75 kW
(1 HP)
1.5 kW
(2 HP)
2.2 kW
(3 HP)
4.0 kW
(5 HP)
Parameter Type Read & Write Minimum 0 Volts
230V 3 Volts 3 Volts 3 Volts 3 Volts 3 Volts N/A
This parameter sets the DC boost level for
lti h[DC B t S l t] ittR
Units 1 Volt Maximum 25% of
MDi
460V 12 Volts 12 Volts 12 Volts 9 Volts 6 Volts 6 Volts
p
acceleration when [DC Boost Select] is set to ‘‘Run
Boost” or ‘‘Break Point.”
Max. Drive
Rated Volts
Figure 5.10 Start/Run Boost
[Base Voltage]
[Base Frequency]
b
0 –
0
Voltage
Frequency
[Start Boost] '
[Run Boost] '
Active when [DC Boost Select] is set to ‘‘Run Boost”
a
150% of Start Boost
a 150% of Run Boost
[Run Boost]
Parameter # 83 Factory Default 0 Volts
[Run
Boost]
Parameter Type Read & Write Minimum 0 Volts
This parameter sets the DC boost level for constant speed
level when [DC Boost Select] is set to ‘‘Run Boost.” [Run
Boost] must be set at a value less than [Start Boost].
Units 1 Volt Maximum 25% of Max. Drive Rated Volts
efesotomasyon.com - Allen Bradley,Rockwell,plc,servo,drive

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley 1305 Series and is the answer not in the manual?

Allen-Bradley 1305 Series Specifications

General IconGeneral
Series1305
DimensionsVaries by model
WeightVaries by model
Frequency Range50-60 Hz
Control MethodVolts per Hertz
Communication InterfaceRS-485
Enclosure TypeIP20
Storage Temperature-40-70°C
Humidity5 to 95% non-condensing

Related product manuals