Programming
5-37
This group of parameters contains the programming options for digital and analog drive outputs.
Output
Configura-
tion
[Out
p
ut 1 Confi
g
]
Parameter # 90 Factory Default “Faulted“
[Output
1
Config]
Parameter Type Read & Write
This parameter sets the condition that actuates the relay Units Text Settings ‘‘At Speed”
Output closes when drive reaches [Freq Command].
This
parameter
sets
the
condition
that
actuates
the
relay
output at TB2, terminals 9 and 10.
‘‘Above Freq”
Output closes when drive exceeds value set in
[Above Freq Val].
‘‘Running”
Output closes when drive is running.
‘‘Faulted”
Output closes when drive is faulted.
‘‘Alarm”
Output closes when the drive reaches hardware
current limit, software current limit, overvoltage, line
loss or 4-20 mA loss.
‘‘Above Curr”
Output closes when current exceeds value set in
[Above Curr Val].
[
Out
p
ut 2 Confi
g]
Parameter # 91 Factory Default “Running”
[Output
2
Config]
Parameter Type Read & Write
This parameter sets the condition that actuates the open
Units Text Settings ‘‘At Speed”
Output closes when drive reaches [Freq Command].
This
parameter
sets
the
condition
that
actuates
the
open
collector output at TB2, terminals 19 and 20.
‘‘Above Freq”
Output closes when drive exceeds value set in
[Above Freq Val].
‘‘Running”
Output closes when drive is running.
‘‘Faulted”
Output closes when drive is faulted.
‘‘Alarm”
Output closes when the drive reaches hardware
current limit, software current limit, overvoltage, line
loss or 4-20 mA loss.
‘‘Above Curr”
Output closes when current exceeds value set in
[Above Curr Val].
Application Note: During power up of the drive, the customer programmable Outputs 1 & 2 (TB2–9 & 10, TB2– 19 & 20) are in an indeterminate
state for a period of time until the internal control of the drive has initialized (3 sec. max.). Any control system connected to the programmable outputs
should take this into consideration. On power down, the programmable outputs may transition in a similar way.
efesotomasyon.com - Allen Bradley,Rockwell,plc,servo,drive

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley 1305 Series and is the answer not in the manual?

Allen-Bradley 1305 Series Specifications

General IconGeneral
BrandAllen-Bradley
Model1305 Series
CategoryController
LanguageEnglish

Related product manuals