88 Rockwell Automation Publication 1734-UM018D-EN-E - September 2017
Appendix A Specifications
Emissions CISPR 11:
Group 1, Class A
ESD immunity IEC61000-4-2:
6 kV contact discharges
8 kV air discharges
Radiated RF immunity IEC 61000-4-3:
10V/m with 1 kHz sine-wave 80% AM from 30...2000 MHz
10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz
10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz
10V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz
EFT/B immunity IEC 61000-4-4:
±4 kV @ 5 kHz on power ports
±3 kV @ 5 kHz on communications ports
Surge transient immunity IEC 61000-4-5:
±1 kV line-line (DM) and ±2 kV line-earth (CM) on power ports
±2 kV line-earth (CM) on communications ports
Conducted RF immunity IEC 61000-4-6:
10Vrms with 1kHz sine-wave 80% AM from 150kHz...80MHz
North American temp code T4A
IEC Temp Code T4