Rockwell Automation Publication 1791ES-UM001G-EN-P - November 2016 133
Get Diagnostic Status from Modules by Using Explicit Messaging Appendix A
Place these rungs in the standard task.
Figure 66
Figure 70 show the MSG instruction parameters to read
Instance 852 from the 1732ES-IB8XOBV4 module. See Appendix C
of
this manual for a layout of possible instances.
Figure 66 - Instance 852 Configuration Tab
From the top of the Message Configuration dialog box, choose the
Communication tab. This dialog box requires the path to the module.
Click Browse to go to the module that the MSG reads.