EasyManua.ls Logo

Allen-Bradley 1791ES-IB8XOBV4 - Page 158

Allen-Bradley 1791ES-IB8XOBV4
176 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
158 Rockwell Automation Publication 1791ES-UM001G-EN-P - November 2016
Appendix B Safety Data
1732ES-IB12XOBV2 Single Channel Inputs 2.7190E-07 2.7190E-07 5.8410E-10
Dual Channel Inputs 3.0730E-07 3.0730E-07 2.0350E-10
Dual Channel Outputs 3.7360E-07 3.7360E-07 2.0820E-10
1732ES-IB12XOB4 Single Channel Inputs 2.7190E-07 2.7190E-07 5.8410E-10
Dual Channel Inputs 3.0730E-07 3.0730E-07 2.0350E-10
Single Channel Outputs
(2)
2.8910E-07
(2)
2.8910E-07
(2)
6.4630E-09
(2)
Dual Channel Outputs 3.5140E-07 3.5140E-07 2.0660E-10
1732ES-IB8XOBV4 Single Channel Inputs 2.7190E-07 2.7190E-07 5.8410E-10
Dual Channel Inputs 3.0730E-07 3.0730E-07 2.0350E-10
Dual Channel Outputs 3.7360E-07 3.7360E-07 2.0820E-10
1732ES-IB8XOB8 Single Channel Inputs 2.7190E-07 2.7190E-07 5.8410E-10
Dual Channel Inputs 3.0730E-07 3.0730E-07 2.0350E-10
Single Channel Outputs
(2)
2.8910E-07
(2)
2.8910E-07
(2)
6.4630E-09
(2)
Dual Channel Outputs 3.5140E-07 3.5140E-07 2.0660E-10
1732ES-IB16 Single Channel Inputs 2.7190E-07 2.7190E-07 5.8410E-10
Dual Channel Inputs 3.0730E-07 3.0730E-07 2.0350E-10
(1) These failure rates assume that a module's inputs or outputs are represented by a single block in a reliability block diagram (the
single channel rates should be applied to the reliability block if the module is configured in Single Channel mode, the dual
channel rates should be applied to the reliability block if the module is configured in Dual Channel mode).
(2) Single channel output mode (1732ES-IB12XOB4 and 1732ES-IB8XOB8 only) is only valid for applications with Process Safety
Times ≥ 600msec OR with Demand Rates ≤ 1 Demand per Minute.
Table 66 - Failure Rate Data (failures per hour)
(1)
Cat. No. I/O Configuration λ
S
λ
DD
λ
DU

Table of Contents