Publication 1756-UM001G-EN-P - January 2007
Develop Motion Applications 95
Set Up Each SERCOS
Interface Module
To set the data rate and cycle time for each SERCOS interface module
in your project, perform this procedure.
1. In the I/O configuration tree in RSLogix 5000 programming
software, right-click your module and select Properties.
The Module Properties dialog appears.
2. Click the SERCOS Interface tab.
3. From the Data Rate pull-down menu, choose Auto Detect.