8 Rockwell Automation Publication 6000-IN100A-EN-P - August 2020
Preface
Environmental Conditions • Elevation above sea level must be less than 1000 m (3250 ft)
(a)
.
• Ambient air temperature must be between 0…40 °C (32…104 °F)
(b)
.
• Relative humidity must be less than 95%, noncondensing.
• Operation Vibration limited to 3M3(a) per IEC60721-3-3.
• G2 rating with 60% humidity – Storage, Transport, and Operation – as
per ISA 71.04-2013.
• The drive must be installed indoors; there must be no dripping water or
other fluids in the room.
• Cooling air must be clean without significant concentrations of sand,
corrosive or conductive dust, or explosive gas. The drive must be installed
in a Pollution Degree 2 environment as per IEC 61800-5.
• Free from significant vibration.
• The drive must be anchored on a level floor. Please refer to the dimension
drawing for the anchor point sizes and locations.
For the equipment to operate in conditions other than those specified, consult
the local Rockwell Automation Sales Office.
(a) Options are available for operation up to 5000 m.a.s.l. However, these must be stated at the
time of order and cannot be retrofitted in the field.
(b) Options are available for ambient temperatures up to 50 ºC. However, these must be stated
at the time of order and cannot be retrofitted in the field.