Air Conditioning Sizing If the drive is located in an enclosed space, install air conditioners for each
drive. A general formula to calculate air conditioner power required:
Air Conditioning Size (tons)
This is for a general estimate. See the actual heat loss data to calculate air
conditioning sizing. Contact the local Rockwell Automation office for actual
data.
EXAMPLE
For a 1000 kW drive with 96.5% efficiency:
tons of AC required
DriveRating kW1 DriveEfficiency–
3.5
--------------------------------------------------------------------------------------------------------
=
1000 1 0.965
·
–
3.5
---------- ------ ---- ------ ----- ------ ------
10=