P3.08 Reserve Reserve - - * 0408
P3.09 Reserve Reserve - - * 0409
P3.10 Reserve Reserve - - * 040A
P3.11 Reserve Reserve - - * 040B
P3.12 Reserve Reserve - - * 040C
P3.13
X terminal filter
time
X terminal filter
time
0.002s~1.000s 0.010s ○ 040D
P3.14 Reserve Reserve - - * 040E
P3.15
Operation mode
setting
Operation mode
setting
0: Two-wire operation mode 1
1: Two-wire operation mode 2
2: Three-wire operation mode
1 - self hold function
(attach any one of X1 ~
X5 terminals)
3: Three-wire operation mode
2 - self hold function
(attach any one of X1 ~
X5 terminals)
0 × 040F
P3.16
Terminal UP /
DOWN
Speed
UP / DOWN
speed
0.01~99.99Hz/s
1.00
Hz/s
○ 0410
P3.17
Amplitude of UP /
DOWN set point
Amplitude of UP
/ DOWN set
point
0.00~upper limit frequency
10.00
Hz
× 0411
P3.18
Digital frequency
UP / DOWN
storage options
UP / DOWN
storage options
0: UP / DOWN set point is
reset to 0 after receiving
STOP
1: UP / DOWN set point not is
reset to 0 after receiving
STOP, which will not save
after power off
2: UP / DOWN set point not is
reset to 0 after receiving
STOP, which will save
after power off; when
P0.03 is set to 1, P0.02
adjusts power failure
saving online.
2 × 0412
P3.19
D0 terminal
function
D0 terminal
function
0: NULL not defined
1: RUN
2: FAR frequency reaching
3: FDT frequency detection
4: FDTH upper limit
frequency reaching
5: FDTL lower limit
frequency reaching
6: upper and lower limits of
wobble frequency
7: Inverter is in zero speed
operation
8: Simple PLC stage
operation completion
indication
0 × 0413