Modbus Communication Interface | A-7
28 Serial comunication mode (SerialMode= 26 Hex) - 1 r,w
29 Slave address (NodeAddress= 27 Hex) - 1 r,w
30 Baud rate (Baud= 25 Hex) - 1 r,w
31 Modbus protocol setting (ParityAndStop= 92 Hex) - 1 r,w
32 Counts to voltage coefficient (AD16Offset= 01 Hex) - 1 r,w
33 Sensor assembly setting (RefPeriod= 04Hex) sec 1 r,w
34 Sensor assembly setting (SmplPeriod= 05 Hex) sec 1 r,w
35 Sensor temperature coefficient (CellTempSpan
-
100 r,w
= 06 Hex)
36 Sensor temperature coefficient (CellTempOffset=
-
10 r,w
07 Hex)
37 Process pressure coefficient (CustomerSpan= 08 Hex) - 1000 r,w
38 Process pressure coefficient (CustomerOffset= 09 Hex) - 100 r,w
39 Sensor pressure filter coefficient - 100 r,w
(Pressure1Filter= 0A Hex)
40 Flow filter coefficient (FlowFilter= 0B Hex) - 100 r,w
41 Sensor temperature filter coefficient
-
100 r,w
(CellTempFilter= 0C Hex)
42 Process pressure filter coefficient
-
100 r,w
(CustomerFilter= 0D Hex)
43 Current output conversion parameter
-
1 r,w
(MaOutSpan= 0E Hex)
44 Current output correction parameter
-
10 r,w
(MaOutOffset= 0F Hex)
45 Current output coefficient (AnalogOutSpan= 10 Hex) - 1 r,w
46 Current output coefficient (AnalogOutOffset= 11 Hex) - 1 r,w
47 Process pressure coefficient (ProcessSpan= 12 Hex) - 10 r,w
48 Process pressure coefficient (ProcessOffset= 13 Hex) - 10 r,w
49 Flow control parameter (ProBandLoop1= 16 Hex) - 1 r,w
50 Flow control parameter (TsLoop1= 17 Hex) - 1 r,w
51 Flow control parameter (TiLoop1= 18 Hex) - 1 r,w
52 Flow control parameter (SetPointLoop1= 19 Hex) - 1 r,w
53 Flow control parameter (ActuatorLoop1= 1A Hex) - 1 r,w
54 Flow control parameter (uMaxLoop1= 1B Hex) - 10 r,w
REG DEFINITION UNITS SCALING ACCESS
TABLE A-1 cont.