EasyManua.ls Logo

Amtech Axpert-Eazy Series - Page 161

Amtech Axpert-Eazy Series
242 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Axpert-Eazy AC Variable Frequency Drive
6-115
6
Sr.
No.
Command
Name
Op
-
Code
DATA1
DATA2
DATA3
Description
56 DISPLAY_FLG 062 X1 (0-7) Flag (n) 000 It will display value of selected Flag (n) on X1 bit
location.
57 LPF1 063 Register (n)
Register
(m)
Tc (0-100)
Inputs = Register (m) and Tc (in mS)
LPF Output = Register (n)
58 LPF2 064 Register (n)
Register
(m)
Tc (0-100)
59 LPF3 065 Register (n)
Register
(m)
Tc (0-100)
60 LPF4 066 Register (n)
Register
(m)
Tc (0-100)
61 JMPC 067 X (1-100) Flag (n) 000 If Flag (n) = 1, then JUMP to X Command no.
62 JMPNC 068 X (1-100) Flag (n) 000 If Flag (n)! = 1, then JUMP to X Command no.
Range of n, n1, n2 and m are 0 to 114 for register and 0 to 99 for flag.
Register 0 to 85 have Read and Write access. Register 86 to 114 are Read Only.
Flag status is single bit locations, which is 0 to 99.
Memory Locations for Registers and Flag status are different.
X1 indicate Display parameter (M313 to M323)
X indicates Command No.

Table of Contents