EasyManua.ls Logo

Amtech Axpert-Eazy Series - Page 218

Amtech Axpert-Eazy Series
242 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Amtech
A.2
13
A
Power Source
200 ~ 240VAC, 3-Phase, 3-Wire, 50/ 60 Hz
Tolerance
Voltage tolerance: -15%, +10%, Frequency tolerance: ±5%
AMT
-
XXX
-
2
011 015 018 022 030 037 045 055 075 090
Normal Duty
Rated Capacity (Hp) 15 20 25 30 40 50 60 75 100 125
Max Continuous Rated
Current (A)
(Note: 1)
46 61 76 88 110 147 175 215 255 328
Max Applicable Motor
(kW)
(Note: 2)
011 015 018 022 030 037 045 055 075 090
Overload Current Rating
120% for 60 seconds, 140% for 2.5 seconds every 5 minutes
Heavy Duty
Rated Capacity (Hp) 10 15 20 25 30 40 50 60 75 100
Max Continuous Rated
Current (A)
(Note: 1)
37 46 61 76 88 110 147 175 215 255
Max Applicable Motor
(kW)
(Note: 2)
7.5 011 015 018 022 030 037 045 055 075
Overload Current Rating
150% for 60 seconds, 175% for 2.5 seconds every 5 minutes

Table of Contents