EasyManuals Logo

Antec controls LUME20 User Manual

Antec controls LUME20
53 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #27 background imageLoading...
Page #27 background image
LUME20 - MANUAL
27 | LUME20Manual | AntecControls.com
Monitored Room - Settings
This section details all the available options for each monitored room.
NOTE: If the active room mode has alarms turned off, the alarms and cautions configured below will not activate.
Menu Items
Available
Options/Range
Default
Value
Description
Room Name
19 Characters
Room 1
Adjust the room name.
NOTE: This name will display in the
BACnet object name for points
associated with the room.
Pressure Mode
Positive
Negative
Positive
Adjust the pressure mode of the
monitored room.
Monitored
Sensor
All configured pressure
inputs or None
Sensor on
UI1 (from
Setup
Wizard)
Adjust the sensor for the room.
NOTE: If ‘None’ is selected, the
pressure reading on the home screen
will display as ‘--'.
Monitored
Device 1/
Monitored
Device 2/
Monitored
Device 3
All configured Analog
Inputs (excluding
pressure inputs), all
configured BACnet
Polling Points or None
None
Add additional environmental readings
to be displayed on the Home Screen.
To remove a reading from home screen
display, select ‘None’.
NOTE: Analog Inputs must be
configured in the Inputs menu and
BACnet Polling Points must be
configured in the BACnet Polling Points
menu before they can be selected
here.
Low Pressure
Alarm
Activation Point
Delay
On
Off
-1.0 to +1.0 in.w.c
(-249.1 to +249.1 Pa)
0 to 100,000 seconds
On
+0.01 in.w.c.
(+2.5 Pa)
10 seconds
Set the activation point for the Low
Pressure Alarm as well as the time
delay. The Low Pressure Alarm is used
to indicate if the room is too close to
neutral. i.e. not pressurized enough.
High Pressure
Alarm
Activation Point
Delay
On
Off
-1.0 to +1.0 in.w.c
(-249.1 to +249.1 Pa)
0 to 100,000 seconds
On
+0.05 in.w.c.
(+2.5 Pa)
10 seconds
Set the activation point for the High
Pressure Alarm as well as the time
delay. The High Pressure Alarm is used
to indicate if the room is too negative
or positive (depending on Pressure
Mode). i.e. over pressurized.
Low Pressure
Caution
Activation Point
Delay
On
Off
-1.0 to +1.0 in.w.c
(-249.1 to +249.1 Pa)
0 to 100,000 seconds
Off
Set the activation point for the Low
Pressure Caution, as well as the time
delay.
High Pressure
Caution
Activation Point
Delay
On
Off
-1.0 to +1.0 in.w.c
(-249.1 to +249.1 Pa)
0 to 100,000 seconds
Off
Set the activation point for the High
Pressure Caution, as well as the time
delay.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Antec controls LUME20 and is the answer not in the manual?

Antec controls LUME20 Specifications

General IconGeneral
BrandAntec controls
ModelLUME20
CategoryMonitor
LanguageEnglish