Outputs
This section details configuration instructions and available settings for Analog Outputs and Binary Outputs. Configured outputs
will display the output name below the output header in the Outputs menu. Outputs that are not configured for a specific usage
(i.e. usage set to ‘None’) will display ‘Available’.
NOTE: A maximum of one Analog Output and two Binary Outputs can be configured per LUME20.
Analog Output Room Pressure
Used to output the current room pressure reading of a specific pressure input via an analog signal. Primarily used when a third-
party device requires a room pressure reading from LUME20 for either monitoring or control purposes.
The following settings are available if the Usage is Room Pressure.
Menu Items
Available
Options/Range
Default Value
Description
Output
Name
19 Characters
Pressure Output
Adjust the output name.
NOTE: This name will display in the
BACnet object name.
Voltage
Range Min.
0 to 10 VDC
2 VDC
Set the minimum value for the voltage
range. The voltage entered here must
match the minimum voltage for the
device providing the signal to LUME20.
Voltage
Range Max.
0 to 10 VDC
10 VDC
Set the maximum value for the voltage
range. The voltage entered here must
match the maximum voltage for the
device providing the signal to LUME20.
Pressure
Range Min.
-1.0 to +1.0 in.w.c
(-249.1 to +249.1 Pa)
-0.25 in.w.c.
(-62.2 Pa)
Set the minimum value for the pressure
range. The pressure entered here must
match the minimum pressure for the
device providing the signal to LUME20.
Pressure
Range Max.
-1.0 to +1.0 in.w.c
(-249.1 to +249.1 Pa)
+0.25 in.w.c.
(+62.2 Pa)
Set the maximum value for the
pressure range. The pressure entered
here must match the maximum
pressure for the device providing the
signal to LUME20.
Pressure
Input
All configured
pressure inputs or
None
None
Adjust the sensor to use as the
pressure value to output. When ‘None’
is selected, the AO will output the
voltage that corresponds to 0 in.w.c. (0
Pa).
Current
Value
Read only value
The current pressure sensor value with
scale factor, offset and reverse reading
applied. This reading matches the value
displayed on the Home Screen when
set as the monitored sensor.
Current
Voltage
Read only value
The current voltage of the AO.