34 | LUME20 – Manual | AntecControls.com
Outputs
This section details configuration instructions and available settings for Analog Outputs and Binary Outputs. Configured outputs
will display the output name below the output header in the Outputs menu. Outputs that are not configured for a specific usage
(i.e. usage set to ‘None’) will display ‘Available’.
NOTE: A maximum of one Analog Output and two Binary Outputs can be configured per LUME20.
Analog Output – Room Pressure
Used to output the current room pressure reading of a specific pressure input via an analog signal. Primarily used when a third-
party device requires a room pressure reading from LUME20 for either monitoring or control purposes.
The following settings are available if the Usage is Room Pressure.
Options/Range
Name
NOTE: This name will display in the
Range Min.
Set the minimum value for the voltage
range. The voltage entered here must
match the minimum voltage for the
device providing the signal to LUME20.
Range Max.
Set the maximum value for the voltage
range. The voltage entered here must
match the maximum voltage for the
device providing the signal to LUME20.
Range Min.
(-249.1 to +249.1 Pa)
(-62.2 Pa)
Set the minimum value for the pressure
range. The pressure entered here must
match the minimum pressure for the
device providing the signal to LUME20.
Range Max.
(-249.1 to +249.1 Pa)
(+62.2 Pa)
Set the maximum value for the
pressure range. The pressure entered
here must match the maximum
pressure for the device providing the
Input
pressure inputs or
None
Adjust the sensor to use as the
pressure value to output. When ‘None’
is selected, the AO will output the
voltage that corresponds to 0 in.w.c. (0
Value
The current pressure sensor value with
scale factor, offset and reverse reading
applied. This reading matches the value
displayed on the Home Screen when
set as the monitored sensor.
Voltage
The current voltage of the AO.