27Tensor
Finally save new value with button [M], thereby the next menu item will be activated automatically.
Defaults for the set values of the end positions must cover at least 20% of full scale,
otherwise the error "PE" - "Parameter Error" is reported.
Example: Range 1..5 V => Covering (5-1) V x 20% = 0.8 V
Lower end position 0.5 V => Upper end position min. 0.5 V+0.8 V =1.3 V
8.2.1.3 Actual value output for the end positions C.L / C.i
The actual feedback must be set analog to the set values for both end positions.
C.L
C.t
Set with DIP switches 1 and 2 how the actual value is used, see chapter 7.2.
Select menu item „CL“ or „Cr“ and conrm with button [M].
Set the actual value (see 7.2):
− DIP1/DIP2 – ON/OFF: 0…10 V
− DIP1/DIP2 – OFF/ON: 0... 20 mA
Finally save the new value with button [M], thereby the next menu item will be activated automatically.
Defaults for the actual limits of the end positions must cover at least 20% of full scale,
otherwise the error "PE" - "Parameter Error" is reported.
Example: Set range 4 mA => Covering 4 mV x 20% = 0.8 mA
Lower end position 0.1 mA => Upper end position min. 0.9 mA (=0.1+0.8)
Set-up operation I-ACT (PMR)
0 mA
(0 V optional)
4 mA
(2 V optional)
20 mA
(5 bzw. 10 V optional)
free values [mA]
([V] optional)
ADVICE
!
ADVICE
!
Set slide switch in position „MANU“
Press button „Menu“ > for 2 sek.
Set-up operation active, Display indicates 1. Menu item