EasyManuals Logo

Aritech 2X Series User Manual

Aritech 2X Series
140 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #63 background imageLoading...
Page #63 background image
Chapter 3: Configuration and commissioning
2X Series Installation Manual 57
Therefore, in Repeater mode the panel uses the network:
To process and display the events received from any remote panel that affect
the local zones in the system
To display any event coming from any of the remote panels present in the
repeated panel map (or as defined by the event filter configuration)
To change the network operation mode settings:
1. Select Panel setup from the Main menu.
2. Select Firenet, and then select Firenet Opmode.
3. Select Standalone, Networked, or Repeater).
4. Press F4 (Enter), and then press F1 (Back).
5. Press F1 (Save), F3 (Apply), F4 (Discard), or F2 (Exit).
Remember to apply saved settings from the Main menu.
A stand-alone panel retains its network node even though it is not communicating
with the network.
Repeater map
The default setting is YES (all control panels in the fire network are repeated).
To change the repeater map settings:
1. Select Panel setup from the Main menu.
2. Select Firenet, and then select Repeater map.
3. Select the control panel from the list, and then select YES (to repeat the
control panel) or NO (to stop repeating the control panel).
4. Press F4 (Enter), and then press F1 (Back).
5. Press F1 (Save), F3 (Apply), F4 (Discard), or F2 (Exit).
Remember to apply saved settings from the Main menu.
Global controls
Select the Global controls option to allow the control panel to control the fire
network (by sending global commands defined by the command filter). The
default setting is YES (global commands are allowed).
To change the Global control settings:
1. Select Panel setup from the Main menu.
2. Select Firenet, and then select Global controls.
3. Select the control panel from the list, and then select YES (to allow global
control) or NO (to stop global control).
4. Press F4 (Enter), and then press F1 (Back).

Table of Contents

Other manuals for Aritech 2X Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Aritech 2X Series and is the answer not in the manual?

Aritech 2X Series Specifications

General IconGeneral
CertificationsEN54-2, EN54-4
Power Supply230V AC, 50Hz
Battery Capacity7Ah
Current ConsumptionStandby: 50mA
Humidity RangeUp to 95% RH, non-condensing