- 57 -
Hydraulic confi guration Hot water
General Confi guration
Time programming
Setting setpoint T°
Anti-legionella management
▼
Hot Water (HW)
"Comfort T° charge": DHW program + off -peak hours / Off -peak hours / Permanent.
Electrical back-up power: 0.1 to 10 KW.
Confi guration
Comfort T° charge
Electrical back-up power
1KW
DHW Circuit
DHW program + off -peak hours
Use the same procedure as the time program of heating periods. Resume from the step
2
(See "Time programming",
page 56).
DHW period factory setting: 00:00 - 05:00, 14:30 - 17:00.
"Comfort T°": ECO Temp Setpoint … 80°C.
"ECO T°": 8°C... Comfort Temp setpoint.
DHW temperature factory settings: Comfort 55°C, ECO 40°C.
Setpoint settings
Comfort T°
55°C
ECO T° 40°C
DHW Circuit
"Anti-legionella": Stop, ON.
"Day of treatment": Monday / Tuesday / Wednesday / Thursday / Friday / Saturday /
Sunday.
"Hour of treatment": 00:00.
"Setpoint T°": 55°C... 75°C.
Anti-legionella management
Day of treatment Sunday
Anti-legionella
Stop
Hour of treatment ---
Setpoint T° 60°C
DHW Circuit
Alfea Extensa A.I. R32 / INSTALLATION / 2114 - EN