- 86 -
Unit Dimensions without undercarriage (LxWxH) 2262 x 1050 x 1492 mm 2262 x 1050 x 1492 mm
Dimensions without undercarriage, with optional 24h fuel tank (LxWxH) 2262 x 1050 x 1630 mm 2262 x 1050 x 1630 mm
Weight net mass 1328 kg 1328 kg
Weight net mass - with optional 24h fuel tank 1381 kg 1381 kg
Notes
1) Reference conditions for engine performance to ISO 3046-1.
2) See derating diagram below or consult the factory for other conditions.
3) At reference conditions unless otherwise stated.
4) Rating definition (ISO 8528-1):
LTP: Limited Time Power is the maximum electrical power which a generating set is capable of delivering (at variable load), in the event of a
utility power failure (for up to 500 hours per year of which a maximum of 300 hours is continuous running). No overload is permitted on these
ratings. The alternator is peak continuous rated (as defined in ISO 8528-3) at 25°C.
PRP: Prime Power is the maximum power available during a variable power sequence, which may be run for an unlimited number of hours per
year, between stated maintenance intervals and under the stated ambient conditions. A 10% overload is permitted for 1 hour in 12 hours. The
permissible average power output during a 24h period shall not exceed the stated load factor as indicated in the ‘Technical specifications’
above.
5) Specific mass fuel used: 0.86 kg/l.