EasyManua.ls Logo

AuCom EMX3-1600C - Page 44

AuCom EMX3-1600C
96 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
PROGRAMMING MENU
6M
Remote Reset Logic
Normally Closed
6N
Analog Input Trip
Do Not Trip
6O
Analog Input Scale
2-10 V
6P
Analog Trip Point
50%
6Q
Local/Remote
LCL/RMT Anytime
6R
Comms in Remote
Enable Control in RMT
7
Outputs
7A
Relay A Function
Main Contactor
7B
Relay A On Delay
0m:00s
7C
Relay A Off Delay
0m:00s
7D
Relay B Function
Run
7E
Relay B On Delay
0m:00s
7F
Relay B Off Delay
0m:00s
7G
Relay C Function
Trip
7H
Relay C On Delay
0m:00s
7I
Relay C Off Delay
0m:00s
7J
Relay D Function
Off
7K
Relay E Function
Off
7L
Relay F Function
Off
7M
Low Current Flag
50%
7N
High Current Flag
100%
7O
Motor Temperature Flag
80%
7P
Analog Output A
Current (% FLC)
7Q
Analog A Scale
4-20 mA
7R
Analog A Maximum Adjustment
100%
7S
Analog A Minimum Adjustment
000%
7T
Analog Output B
Current (% FLC)
7U
Analog B Scale
4-20 mA
7V
Analog B Maximum Adjustment
100%
7W
Analog B Minimum Adjustment
000%
8
Display
8A
Language
English
8B
F1 Button Action
Auto-Start/Stop Menu
8C
F2 Button Action
None
8D
Display A or kW
Current
8E
User Screen - Top Left
Starter State
8F
User Screen - Top Right
Blank
8G
User Screen - Bottom Left
Hours Run
8H
User Screen - Bottom Right
Analog Input
8I
Graph Data
Current (% FLC)
8J
Graph Timebase
10s
8K
Graph Maximum Adjustment
400%
8L
Graph Minimum Adjustment
000%
8M
Current Calibration
100%
8N
Mains Reference Voltage
400 V
8O
Voltage Calibration
100%
User Manual (710-04840-00M) | 43

Table of Contents

Related product manuals