CONTROLLER
MVE User Manual (710-17074-00G) | 47
2B – Start Ramp Time
Range:
0:01 - 3.00 (minutes:seconds)
1 second
Sets the ramp time for current ramp starting (from the initial current to the current limit).
2C – Initial Current
Range:
50% - 600% FLC
400%
Sets the initial start current level for current ramp starting, as a percentage of motor full load current. Set so
that the motor begins to accelerate immediately after a start is initiated.
If current ramp starting is not required, set the initial current equal to the current limit.
2D – Current Limit
Range:
50% - 600% FLC
400%
Sets the current limit for constant current and current ramp soft starting, as a percentage of motor full load
current.
2E – Reserved
Description:
This parameter is reserved for future use.
2F – Kickstart Time
Range:
0 – 2000 milliseconds
0000 milliseconds
Sets the kickstart duration. A setting of 0 disables kickstart.
2G – Kickstart Level
Range:
100% - 700% FLC
500%
Sets the level of the kickstart current.
Kickstart subjects the mechanical equipment to increased torque levels. Ensure the motor, load and couplings can
handle the additional torque before using this feature.
Coast To Stop (default)
TVR Soft Stop
Selects the stop mode.
0:00 - 4:00 (minutes:seconds)
0 second
Sets the time for soft stopping the motor using timed voltage ramp.
If a main contactor is installed, the contactor must remain closed until the end of the stop time.
3 Auto-Stop
The MVE can be programmed to stop automatically, after a specified delay or at a specified time of day.
This function should not be used in conjunction with remote two-wire control.
The soft starter will still accept start and stop commands from the remote inputs or serial communication network. To
disable local or remote control, use parameter 6Q.
3A, 3B – Reserved
Description:
These parameters are reserved for future use.
The soft starter will not auto-stop.
Timer The soft starter will auto-stop after a delay from the next start, as specified in parameter 3D.
Clock The soft starter will auto-stop at the time programmed in parameter 3D.
Selects whether the soft starter will auto-stop after a specified delay, or at a time of day.